Extra Standard construction with cable tray of the ceiling type

Overview

Example of the Extra Standard construction with cables in a cable tray of the ceiling type- tested with the cables of BITNER

Fastening with a threaded rod to the ceiling:

  • indirectly with the USOV grip and PSROM10 expandable sleeve bolt to the ceiling;
  • directly with the TRSOM10 expandable sleeves - no USOV grip required for a sleeve sunk min. 60 mm into the concrete foundation.

Extra Standard cable tray width:400 mm.

Extra Standard cable tray sheet thickness:1, 2 mm.

Extra Standard spacing of supports: 1,5 m.

Maximum load: 10 kg/m.

Back to top ↑

Set elements

O.no. Product Symbol Item number Pcs in suspension
1 KGL/KGOL...H60 Cable Tray KGL/KGOL300H60/3 160416
1
 / 
3,0 m
2 SGK... Screw Set SGKM6x12 651141
7
 / 
3,0 m
3 WMC/WMCO... Bracket WMC/WMCO300 711130
1
 / 
1,5 m
4 UPW/UPWO Rod Grip UPW/UPWO 750100
1
 / 
1,5 m
5 WPCW/WPCO... Ceiling Bracket WPCW/WPCO400 750640
1
 / 
1,5 m
6 PGM... Threaded Rod PGM10/1 651001
1
 / 
1,5 m
7 USV/USOV Rod Hanger USV/USOV 750709
1
 / 
1,5 m
8 PP... Washer PP10 650544
4
 / 
1,5 m
9 NS... Nut NSM10 650244
4
 / 
1,5 m
10 SM... Skrutka (komplet) SMM10x30 650843
2
 / 
1,5 m
11 SGK... Screw Set SGKM8x14 651241
2
 / 
1,5 m
12 SGK... Screw Set SGKM6x12 651141
2
 / 
1,5 m
13 PSRO... Anchor Bolt PSROM10x80 804100
3
 / 
1,5 m
As alternative to the complete set
14 PP... Washer PP10 650544
2
 / 
1,5 m
15 NS... Nut NSM10 650244
2
 / 
1,5 m
16 PSRO... Anchor Bolt PSROM10x80 804100
2
 / 
1,5 m
17 TRSO... Drop-In Anchor - Steel TRSOM10 804800
1
 / 
1,5 m
Add selected to the project Add all to the project
Specify cable channel length [m]:
Calculate
Back to top ↑

Examples

Example of the Extra Standard construction with cables in a cable tray of the ceiling type- tested with the cables BITNER.

Extra Standard cable tray width- 400mm.

Extra Standard spacing of supports- 1,5m.

Extra Standard cable tray sheet thickness- 1,2 mm.

Fastening with a threaded rod to the ceiling:

  • indirectly with an USOV grip and PSROM10 expandable sleeve bolt to the ceiling.
  • directly with theTRSOM10 expandable sleeves - no USOV grip required for a sleeve sunk min. 60 mm into the concrete foundation..
Back to top ↑